DS-CLAMP-200DC

Type
Flux gate sensor
Current Range
200A DC or ACrms
Sensitivity
0.01V/A
Bandwidth
DC to 500kHz
Resolution
±200mA
TEDS
Fully supported
Conductor Position Sensitivity⁷
Max. ±0.1% of reading
Zero Offset (+25°C)
Max. ±10mA
Error due Earth Magnetic Field⁶
Max. 50mA
Temp. Coefficient
±0.01% /°C

Connection

Accuracy⁷

Amplitude Phase Error
DC
±0.3% rdg. ±40mA
to 100 Hz
±0.3% rdg. ±20mA
±0.1°
100 – 500 Hz
±0.3% rdg. ±40mA
±0.2°
500 Hz – 1 kHz
±0.5% rdg. ±40mA
±0.5°
1 kHz – 5 kHz
±1.0% rdg. ±40mA
±1.0°
5 kHz – 10 kHz
±1.5% rdg. ±40mA
±1.5°
10 kHz – 20 kHz
±5% rdg. ±40mA
±(0.5+0.1 f [kHz])°
20 kHz – 50 kHz
±5% rdg. ±40mA
±(0.5+0.1 f [kHz])°
50 kHz – 100 kHz
±15% rdg. ±100mA
±(0.5+0.1 f [kHz])°
100 kHz – 200 kHz
±15% rdg. ±100mA
±(0.5+0.1 f [kHz])°
200 kHz – 300 kHz
±15% rdg. ±100mA
±(0.5+0.1 f [kHz])°
300 kHz – 500 kHz
±30% rdg. ±100mA

General

Dimensions [mm]
153x67x25
Max. Conductor Size
20mm
Power Supply
±11V to ±15V
Current Consumption
Max. 6VA
Operating Environment
Indoors, Pollution Degree II, altitude up to 2000m
Operating Temp.
-40°C to +85°C
Operating Humidity
up to 80% (not condensing)
Safety Standards
EN61010-2-032:2012
EMC Standards
EN61326-1:2013
Rohs
EN50581:2012

Frequency Derating Curves