IT 1000-S

Primary Current Range DC, RMS Sinus
1000 A
Conversation ratio
1:1000
Overload Ability Short Time (100ms)
4000 Apk
Max. burden resistor (100 % of lp)
2.5 Ω
di/dt (accurately followed)
> 100A/µs
Temperature influence
< 1 ppm/K
Output Ratio
1 A @ 1000A
Bandwidth (0.5% of lp)
DC…500kHz
Linearity
<0.001 %
Offset
<0.005 %
Frequency Influence
0.06 %/kHz
Angular Accuracy
<0.025°+0.09°/k Hz
Rated isolation voltage rms, single isolation CAT III,
300 V
2 IEC 61010-1 standards EN 50178 standards polution deg.
300 V
Test voltage 50/60 Hz, 1 min
3.1kV
Inner diameter
30mm
Dimension
128x106x85
Supply voltage (± 5%)
±15V
Operating humidity
20% to 80% (not condensing)
Operating temperature
+10°C to +50°C
DEWESoft® Shunt
1 Ω

Dimensions