IN 1000-S

Primary Current Range DC, RMS Sinus
1000 A
Conversation ratio
1:1500
Overload Ability Short Time (100ms)
5000 Apk
Max. burden resistor (100 % of lp)
4 Ω
di/dt (accurately followed)
> 100A/µs
Temperature influence
< 0.3 ppm/K
Output Ratio
666 mA @ 1000A
Bandwidth (0.5% of lp)
DC…440kHz
Linearity
<0.003 %
Offset
<0.012 %
Frequency Influence
0.1 %/kHz
Angular Accuracy
<0.01°+0.05°/k Hz
Rated isolation voltage rms, single isolation CAT III,
1000 V
2 IEC 61010-1 standards EN 50178 standards polution deg.
Test voltage 50/60 Hz, 1 min
4.2kV
Inner diameter
38mm
Dimension
128x106x54
Supply voltage (± 5%)
±15V
Operating humidity
20% to 80% (not condensing)
Operating temperature
+10°C to +50°C
DEWESoft® Shunt
1 Ω